I’ve been having my butt kicked by a walk in cooler I think I lucked out finally‘s broke when I was there. It’s 404A refrigerant. They would in the past call sale the cooler was running warm I go there and magically running fine. Pressures fine sight glass clear. Today same thing happened after running for a month or so this time it was running with 95 PSI suction 300 to 350 head obviously headmaster was passing discharge gas into liquid line as it was pretty warm. I added some gas didn’t do anything out of desperation as it was full of food, I turned the unit off and let it come back on and miraculously it all started working great. Pressures were great 55 section 250 head pulled down to 34° no problem in the box. Going to replace the headmaster any of you guys seen anything like that a headmaster that would stick like that?