Carell ir33 and a Genesis pressure transducer

Carell ir33 and a Genesis pressure transducer

Original transducer failed and was only sending 1.56 vdc (156 psi) no matter the actual pressure. Ordered the identical transducer directly from the Oem however it now reads 8.14 vdc (814 psi). The original sensor only used 2 wires and the shield, new used 3 plus shield. I’m going to run a new harness but tech support won’t help with the wiring. I think it’s RED 12V+= pin 36 V+. BLACK -Ground= pin 27 -B1. And WHITE signal 1-6 VDC goes in to pin 28 +B1. Thanks in advance.