Monday, August 17, 2020

Custom Freezer plate system

Custom Freezer plate system

I know, it looks kinda ghetto rigged, but i dont want to make it pretty until i get all the bugs worked out.

So ive building this system for about a month. Heres the basics,

  • 18 plates,
  • 1/4th inch evap coils 9 Circuits,
  • 2 plates per circuit
  • 3hp -40 Condenser unit
  • EEV with controller, Temp sensor, pressure sensor 3/8ths in, 1/2 out
  • 9 circuit refrigerant distributor, 1/2 in and 9 circuit 3/16th out

So I did a test run last night, the suction line is getting to -24c and maxing out at that temp,

i think there is a slight amount of liquid returning to the compressor, So ill be installing a suction line accumulator.

3 of the top circuits arent reaching freezing temps, which i think has something to do with the suction line assembly, i might need to split the suction line into 2 sections, 4 circuits on the top, and 5 circuits on the bottom.

If that doesn't work, then ill be replacing the 3/8ths refrigerant distributor with 5/32 inch circuits instead. Which 5/32 was my original design but the dum dums over at the fabrication place made 3/8ths circuits instead of 5/32

So, what do you guys think? the 3 top circuits are most likely a suction line problem?