Monday, September 21, 2026

C02 rack being funny

C02 rack being funny

A system one of our customers has has being doing some funny stuff lately. I grabbed a couple of screenshots of the graphs. From a certain day, the HPV started running 100%, causing higher than usual flash tank pressure, so the FGBV is also trying to run 100%. End result being suction superheat alarms on the MT comps. Looking to go visit the site tomorrow, so will update on findings. But anyone wanna throw opinions based on these sideways uploaded graphs.

submitted by /u/Memory-Repulsive
[link] [comments]